![]() |
||||||||||||||||||||||||||||||||||||||||||||||||||
|
PLUMBING CODE HIGHLIGHTS AND TECHNICAL INFORMATION Backflow preventers and conditioning chemicals Low water fuel cutoff devices Mixing valve requirements to meet Plumbing Code Public Building - Definition Water temperature requirements - maximum allowed Backflow preventers and conditioning chemicals Section 608.16.2 of the 2003 IPC Plumbing Code states that “potable supply to a boiler shall be equipped with a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012 or CAN/CSA B64.3. Where conditioning chemicals are introduced into the system, the potable water connection shall be protected by an air gap or a reduced pressure principle backflow preventer complying with ASSE 1013 CAN/CSA B64.4 or AWWA C511”. TOP Backflow preventers and antifreeze It is the responsibility of the licensed plumber to protect the potable water supply. When you add a chemical to the boiler it is up to the licensed plumber to make sure the potable water supply is protected to meet the code. At this time, the backflow preventer must be changed or installed to meet ASSE 1013 or an air gap made so there is no physical connection to the potable water supply. TOP Mixing valve requirements on a domestic water heater Whenever a new or replacement water heater is installed after Feb. 1, 2005. The definition of a water heater is any device that heats hot water. This requirement also applies to instantaneous heaters that supplies hot water to more than one fixture. TOP Mixing valve requirements to meet the Plumbing Code The mixing valve shall meet ASSE 1017 which is addressed in section 613.1 of the 2003 IPC Plumbing Code. This standard ensures that if for any reason the valve should fail; it fails to the cold position. TOP Maximum hot water temperature allowed 120 degrees Fahrenheit unless otherwise required by law. This is referenced in section 602.2 of the 2003 IPC. A good guideline is that any faucet that you can put your hand under, must meet this requirement. Dishwashers do not have to meet this requirement because you cannot put your hands into them. TOP Low water fuel cut off devices All hot water heating boilers installed after January 1, 1991 shall have the low water fuel cut off installed. TOP The definition is found in the Fire & Building Safety Code regulations effective October 22, 2005. The definition is quite detailed, but a rule of thumb is anything other than an owner occupied single family dwelling. See the Code for actual definitions and descriptions. TOP Low water fuel cut off and test switch Temperature controls in a public building NFPA 31 requires that each individual automatically fired hot water heating or hot water supply boiler shall have a safety limit control that will cut off the fuel supply to prevent water temperature from exceeding the maximum allowable temperature at the boiler outlet. This water temperature safety control shall be constructed to prevent a temperature setting above the maximum allowable temperature. Also, each individual hot water heating or hot water supply boiler or each system of commonly connected boilers without intervening valves shall have a control that will cut off the fuel supply when the temperature reaches an operating limit which shall be less than the maximum allowable temperature. Table A.10-5.4 of NFPA 31 also requires “One manual reset type limit control, which requires local manual intervention to reset”. TOP
|
|||||||||||||||||||||||||||||||||||||||||||||||||
| Vermont Department
of Public Safety | Division of Fire Safety | Telephone: 802.479.7561 This page last edited December 12, 2008 | Send Comments/Suggestions |
||||||||||||||||||||||||||||||||||||||||||||||||||